{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2025-9042","assignerOrgId":"b73dd486-f505-4403-b634-40b078b177f0","state":"PUBLISHED","assignerShortName":"Rockwell","dateReserved":"2025-08-14T13:58:45.428Z","datePublished":"2025-08-14T14:23:58.491Z","dateUpdated":"2025-08-14T15:02:18.647Z"},"containers":{"cna":{"affected":[{"defaultStatus":"unaffected","product":"FLEX 5000 I/O","vendor":"Rockwell Automation","versions":[{"status":"affected","version":"Version 2.011 or below"}]}],"descriptions":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"<span style=\"background-color: rgb(255, 255, 255);\">\n\n<span style=\"background-color: rgb(255, 255, 255);\">A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.</span>\n\n</span>"}],"value":"A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IY8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle."}],"metrics":[{"cvssV4_0":{"Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","Safety":"NOT_DEFINED","attackComplexity":"LOW","attackRequirements":"NONE","attackVector":"NETWORK","baseScore":8.7,"baseSeverity":"HIGH","privilegesRequired":"NONE","providerUrgency":"NOT_DEFINED","subAvailabilityImpact":"NONE","subConfidentialityImpact":"NONE","subIntegrityImpact":"NONE","userInteraction":"NONE","valueDensity":"NOT_DEFINED","vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N","version":"4.0","vulnAvailabilityImpact":"HIGH","vulnConfidentialityImpact":"NONE","vulnIntegrityImpact":"NONE","vulnerabilityResponseEffort":"NOT_DEFINED"},"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}]}],"problemTypes":[{"descriptions":[{"cweId":"CWE-1287","description":"CWE-1287: Improper Validation of Specified Type of Input","lang":"en","type":"CWE"}]}],"providerMetadata":{"orgId":"b73dd486-f505-4403-b634-40b078b177f0","shortName":"Rockwell","dateUpdated":"2025-08-14T15:02:18.647Z"},"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1737.html"}],"solutions":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"Upgrade to version 2.012 or later"}],"value":"Upgrade to version 2.012 or later"}],"source":{"advisory":"SD1737","discovery":"INTERNAL"},"title":"Rockwell Automation FLEX 5000 I/O - Module Fault","x_generator":{"engine":"Vulnogram 0.2.0"}},"adp":[{"metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2025-08-14T14:51:36.300478Z","id":"CVE-2025-9042","options":[{"Exploitation":"none"},{"Automatable":"yes"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"title":"CISA ADP Vulnrichment","providerMetadata":{"orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","shortName":"CISA-ADP","dateUpdated":"2025-08-14T14:51:42.178Z"}}]}}